  
CPS’s staff has experience of testing a wide range of commercial developments including retail units, office developments, schools, hospitals, supermarkets, sports centres and many more. We therefore can offer you advice to help obtain a compliant building first time.
Using CPS’s own designed and manufactured equipment we have the ability to air test small offices / industrial units up to buildings with an envelope area of 50,000m². The equipment ranges from small door fans to 7.5 tonne lorries with our fan on the back.
New Part L2A Regulation:
There is now a testing requirement for buildings above 500m² GIFA.
The test standard has changed for buildings over 500m²GIFA and is now based on the Air Leakage rate that is used in the DER calculation (Design Emission Rate)
Buildings below 500m² GIFA are only exempt from an air test if a leakage rate of 15 m³/m²/h is used to calculate the DER.
Normal and Best Practice:
Building Type |
Air Leakage Rate in m³/h/m² at 50 Pa |
|
Normal Practice |
Best Practice |
Building Regulations |
10 |
|
Offices |
|
|
Naturally Ventilated |
7 |
3 |
Mixed-mode |
5 |
2.5 |
Air Conditioned |
5 |
2 |
Factories & Warehouses |
6 |
2 |
Superstores |
5 |
1 |
Schools |
9 |
3 |
Hospitals |
9 |
5 |
Museums |
1.5 |
1 |
Cold Stores |
0.3 |
0.2 |

|